FPD-7024 | Operation and Installation Guide | 1.0 Overview
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
11
1.2.10 Backup Battery Calculation
Use Table 4 to calculate the standby battery capacity required by NFPA when using the FPD-7024.
Table 4: Standby Battery Capacity Calculations
Device Quantity Standby
Existing/Device
Total
Standby
Alarm
Existing/Devic
e
Total Alarm
FPD-7024 Control panel 1 200 mA 200 mA 380 mA 380 mA
FPC-7034 Four-Point Expander 44 mA 156 mA
D7035/B Octal Relay
1
8 Ma + 30 mA
2
8 Ma + 30 mA
2
D7048/B Octal Driver Module 10 mA 10 mA
FMR-7036 Annunciator Keypad 80 mA 100 mA
D7030X Eight-Point LED Annunciator
1
27 mA 132 mA
D7030X-S2 Eight-Point LED
Annunciator
35 mA 175 mA
D7030X-S8 Eight-Point LED
Annunciator
35 mA 175 mA
D7032 Eight-Point LED Annunciator
Expander
1 mA 90 mA
FMR-7033 Keypad
1
80 mA 100 mA
D7039 MUX Expansion Module 150 mA 150 mA
D7042/B Addressable Eight Point Input 18 mA 18 mA
D7050 MUX Photoelectric Smoke
Detector
0.50 mA 0.56 mA
D7050TH MUX Photoelectric Smoke
Detector
0.50 mA 0.56 mA
FMM-7045 Mux Pull Station 0.55 mA 0.55 mA
D7044 Mux Single Input Fire 0.55 mA 0.55 mA
D7044M Mux Mini Contact Module 0.55 mA 0.55 mA
D7052 Mux Dual Input Fire 0.55 mA 0.55 mA
D7053 Mux I/O Module Fire 0.70 mA 0.70 mA
Smoke Detectors
Bells, Horns, and so on
Other Sensors
Other
Grand Total
Standby
Existing
Grand Total
Alarm Existing
1
The 24 VDC existing requirements for the D7030X, FMR-7033 and D7035 are shown at 75% of the 12 VDC level shown
on the specification sheets for these models. The FPD-7024 regulates 24 VDC power from the battery to 12 VDC for these
accessories.
2
Add 30 mA for each relay activated