EasyManua.ls Logo

Bosch FPD-7024 - Testing Procedures; Personal Identification Numbers (PINs)

Bosch FPD-7024
102 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FPD-7024 | Operation and Installation Guide | 1.0 Overview
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
7
1.0 Overview
1.1 System Overview
This guide applies to control panels
equipped with version V1.00 or later
software.
The FPD-7024 Fire Alarm Control Panel is a fully
integrated hard-wire fire alarm system. It can
support four input points (expandable to 255 using
D7039 Multiplex Expansion Module and the FPC-
7034 Four-Point Expander) and 16 individual users
(expandable to 100 with the D7039). The control
panel has a built-in LCD keypad. Up to four
additional keypads can be used to provide user
interface with the system and programming access
for the installer. The FPD-7024 also includes the
following features:
Built-in dual-line communicator
Menu driven keypad programming
Freely programmable
alphanumeric/alphabetical display
99 event history buffer
16 user codes
UL Listed, CSFM, MEA Approved
When the D7039 Multiplex Expansion Module is
installed, these additional features are available:
247 additional addressable input points
(255 total points)
499 Non-volatile event history buffer
100 user codes
Refer to Figure 1 for the location of the major items
on the FPD-7024 Control Board.
Figure 1: FPD-7024 Control Board
Trouble
Silenced
Power
Alarm
Supervisory Gnd Flt
21 3
4 5 6
7 8 9
#
Enter
0
Prog
*
Back
Disable
Drill
Test
History
Acknowledge
Silence
Reset
R2
HR2
HT2
T2
R1
RH1
TH1
T1
NC 3
COM3
NO 3
NC 2
COM2
NO2
NC 1
COM1
NO 1
SMK+
SMK-
4A+
4B+
4B-
4A-
3A+
3B+
3B-
3A-
2A+
2B+
2B-
2A-
1A+
1B+
1B-
1A-
R B G Y OPTION BUS
AUX-
AUX+
BAT-
24V
BAT+
A+
B+
B-
A-
N
A
C
1
A+
B+
B-
A-
N
A
C
2
1
2
4
3
567
8
9
10
11
1. Telco Terminal Strip
2 - Relay Terminal Strip
3 - Smoke Power Terminal Strip
4 - Zone Input Terminal Strip
5 - Option Bus Terminal Strip
6 - FPC-7034 Point Expander Connector Pins
7 - Keypad
8 - D7039 MUX Expansion Module Connector
Pins
9 - LCD Display
10 - NAC Terminal Strip
11 - Auxiliary Power Terminal Strip

Table of Contents