FPD-7024 | Operation and Installation Guide | 6.0 Installation Guide for UL Listed Systems
.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
81
D185 Reverse Polarity Module
The D185 Reverse Polarity Module is a UL Listed
module that connects the control panel with either
a single set or a pair of leased telephone company
(telco) lines in NFPA 72 remote station
applications. It relays system alarm status
information from the control panel to a monitoring
station. The D185 operates with either 12 VDC or
24 VDC supply.
The module can signal alarm, trouble, and
supervisory conditions. Refer to the D185
Installation Manual (P/N: 32906] for details. shows
the module being used to signal alarm and trouble
conditions only. With a third relay (available from
the eight-relay expansion module) and an
additional leased line, supervisory conditions can
also be signaled.
In the example in Figure 15, Relay 1 must be
programmed to operate on Alarm (Zone 63) and
Relay 2 must be programmed to operate on
Trouble (Zone 62). Program Input 4 to operate as a
Supervisory point. Any alarm causes the voltage to
the monitoring station to be interrupted. Placing the
D185 in test mode causes a SUPERVISORY
TROUBLE 4.
Figure 15: Wiring the D185
RELAY 2
NC2
COM2
D185 MODULE
1 122 3 4 5 6 7 8 9 10 11
GND PWR
-
PWR
+
TRBL
TRIG
ALRM
TRIG
SUPV
TRIG
SUPV
+
SUPV
-
ALRM
-
ALRM
+
SUPV
ZONE
GND
INPUT
POINTS
4A+
FIRE PANEL
SMOKE
POWER
SMK+
SMK-
EARTH
GROUND
COM1
NO1
RELAY 1
TO MONITORING
STATION
2.2K EOL
P/N 25899 or
F01U034504
D275
BLUE
BLUE
YELLOW
BLACK
4A-
4B-
4B+