Appendix D: Programming Defaults List
PROG TIME
SYSTEM: Last date in EE 0000
AUTO TEST
TEST TIME: 0200
TEST FREQ: 1 to 4 hours
DAYLIGHT
SAV:
2- enable
SECURITY
PINS
PROGRAMMER: 9876
USERS: User 1 = 1234
User 2 = 0000
AUTHORITY
USER 1: 2
OTHERS: 0
PROG SYSTEM
TIMERS
SMOKE RESET: 6 seconds
AC FAIL DELAY: 6 hours
AUTO SILENCE: 0 minutes
DISPLAY RATE: 4x.25 = 1 second
AC LINE SYNCH 2 (60- Hz)
OPTION BUS
UPDATE BUS: Queries option buses and updates list of
connected devices.
SETUP
KEYPAD:
0
PIN REQUIRED:
LOCAL: 0- No
REMOTE: 1- Yes
REMOTE PGM 0- disable
PROG INPUTS
POINT NUMBER (1-4/5-8/9-255)
FUNCTION Point Function 1 = 1
Point Function 2 = 2
Point Function 3 = 3
Point Function 4 = 4
Point Function 5 = 5
Point Function 6 = 6
Point Function 7 = 7
Point Function 8 = 8
Point Function 9 - 255 = 10
ALARM/TROUBLE: Trouble On Open
OUTPUT ZONE Point Zone 1 = 1
Point Zone 2 = 2
Point Zone 3 = 3
Point Zone 4 = 4
Point Zone 5 = 5
Point Zone 6 = 6
Point Zone 7 = 7
Point Zone 8 = 8
Point Zone 9 - 19 = 9
Point Zone 20 - 39 = 10
Point Zone 40 - 59 = 11 etc.
VERIFICATION: No
LATCHING: Yes
POINT FUNCTION (1 - 16)
1-3, 5-10, 12-16 4 11
CONFIGURE fire water supv
LOCAL ONLY no no no
SILENCEABLE no no no
LOOP
REPSONSE
fast 16s fast
PROG OUTPUTS
NACs
NAC #1:
CONFIGURATION
:
Steady
ZONE ASSIGNS:
Zone A: 53
Zone B: 61
Zone C: 0
Zone D: 0
NAC #2:
CONFIGURATION
:
Steady
ZONE ASSIGNS:
Zone A: 53
Zone B: 61
Zone C: 0
Zone D: 0