FPD-7024 | Operation and Installation Guide | 5.0 Control Panel Programming
54
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
• Temporal: Output turns on and off to implement the ANSI standard evacuation pattern
(Temporal code 3).
• Wheelock: Output is configured to support Wheelock devices with synchronization capability, including
the ability to silence the horn of a combination horn strobe. The Wheelock configuration is not supported
by remote NACs implemented using a Remote NAC power supply.
• Gentex: Output is configured to support Gentex devices with synchronization capability, including the
ability to silence the horn of a horn strobe combination.
The Gentex option does not synchronize to the UL864 9
th
Edition standard.
• System Sensor: Output is configured to support System Sensor devices with synchronization capability,
including the ability to silence the horn of a horn strobe combination.
After you program the desired pattern configuration, the previous window appears.
If you select 3 from the PROG NACs menu, you are asked to enter four zones to activate this output.
OUTPUT ZONE A (XX)
(00-63):
XX” indicates the existing setting for each of the four output zone settings.
Enter the desired zone to activate this output and press [#/Enter]. You are asked to enter up to four zones (A,
B, C, D). Enter 00 (or leave it set at “00”) for any unused zones to prevent unintentional output activation.
After all four zones are programmed, the previous window appears.
Table 19: Pre-Assigned Zone Quick Reference
Zone Pre-Assigned Condition
52 General Fire Alarm (non-silencing)
53 General Fire Alarm, (silencing)
54 Ground Start
55 General Supervisory, (silencing)
56 General Waterflow, (silencing)
57 Communication Trouble
58 General Supervisory Alarm (non-silencing)
59 Alarm Verification
60 AC Failed
61 General Waterflow Alarm (non-silencing)
62 General Trouble
63 General Alarm, Waterflow Supervisory (non-silencing)