Remote NACs
Shortcut: 0-PROG, 5-PROG OUTPUTS, 1-NACs
Use only with the FPP-RNAC-8A-4C. The display scrolls through the NAC options. Press [2] for REMOTE 1,
[3] for REMOTE 2, [4/] for REMOTE 3, or [5] for REMOTE 4. One of the following windows appears:
REM EXP NAC #1
1 - NAC #1
2 - NAC #2
3 - NAC #3
4 - NAC #4
or
REM EXP NAC #2
1 - NAC #1
2 - NAC #2
3 - NAC #3
4 – NAC #4
or
REM EXP NAC #3
1 - NAC #1
2 - NAC #2
3 - NAC #3
4 - NAC #4
or
REM EXP NAC #4
1 - NAC #1
2 - NAC #2
3 - NAC #3
4 - NAC #4
Press the number key that corresponds with the NAC you want to program. The display scrolls through the
following selections:
PROG NACs
1- (reserved)
2- CONFIGURATION
3- ZONE ASSIGNS
The options for remote NACs are the same as for local NACs.
Output Configuration:
Steady: Programmed to turn on steadily for a fire alarm.
Pulsing: Programmed to pulse for a fire alarm at 0.5 sec on and 0.5 sec off.
Temporal: Programmed to pulse for a fire alarm in Temporal 3.
Zone Assignment: Assign each output up to four zones. ZONE A, B, C, or D (00 = disabled) (1 to 63).
Press the number key that corresponds to your selection. After you program the local NACs, the previous
window appears.
5.5.2 Programming Relays
Shortcut: 0-PROG, 5-PROG OUTPUTS, 2-RELAYS
The main control panel includes three on-board relays (Relay 1, Relay 2, and Relay 3). The FPD-7024 can
also support up to two D7035 Octal Relay Modules (Remote Relay 1 and Remote Relay 2), that offer a total
of 16 remote relays (eight relays per module).
The following window appears:
RELAY OUTPUTS
1- LOCAL
2- REMOTE 1
3- REMOTE 2
4- MULTIPLEX
Press the number key that corresponds to your selection.
The option for multiplex relay programming is visible only if the D7039 Multiplex Expander is
installed.
Local Relays
Shortcut: 0-PROG, 5-PROG OUTPUTS, 2-RELAYS
The display scrolls through the Relay options.
Press [1] for LOCAL. The following window appears: