EasyManua.ls Logo

Bosch FPD-7024 - Table 31: History Log

Bosch FPD-7024
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FPD-7024 | Operation and Installation Guide | Appendix C: Reporting Summary for Fire Communicator
92
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
When the Modem IIIa
2
, SIA or Contact ID reporting formats are used, an additional numeric identifier is sent
with system trouble messages that provide a specific indication of the particular fault. This identifier is also
recorded in the history log. Table 31 lists the numeric identifiers.
Table 31: History Log
Condition System
Event
Condition System
Event
Option bus device at address 1 failed 2 Remote relay module 2 disabled by user 52
Option bus device at address 2 failed 3 Class A, Style 6 wiring failure on MUX bus 53
Option bus device at address 3 failed 4 MUX bus A (9-128) failed 54
Option bus device at address 4 failed 5 MUX bus B (129-255) failed 55
Option bus device at address 5 failed 6 MUX module processor failure 56
Option bus device at address 6 failed 7 Remote NAC module 1, output 1 wiring fault 57
Option bus device at address 7 failed 8 Remote NAC module 1, output 2 wiring fault 58
Option bus device at address 8 failed 9 Remote NAC module 1, output 3 wiring fault 59
Option bus device at address 9 failed 10 Remote NAC module 1, output 4 wiring fault 60
Option bus device at address 10 failed 11 MUX bus A (9-128) hardware failure 61
Option bus device at address 11 failed 12 MUX bus B (129-255) hardware failure 62
Option bus device at address 12 failed 13 NAC 1 disabled by user 63
Option bus device at address 13 failed 14 NAC 2 disabled by user 64
Option bus device at address 14 failed 15 Remote NAC module 2, output 1 wiring fault 65
Option bus device at address 15 failed 16 Remote NAC module 2, output 2 wiring fault 66
DX4020 failed 17 Remote NAC module 2, output 3 wiring fault 67
EEPROM failure 19 Remote NAC module 2, output 4 wiring fault 68
Battery charger failure 20 Remote NAC module 3, output 1 wiring fault 69
Ground fault- wiring short 21 Remote NAC module 3, output 2 wiring fault 70
NAC 1 open wiring 22 Remote NAC module 3, output 3 wiring fault 71
NAC 2 open wiring 23 Remote NAC module 3, output 4 wiring fault 72
Remote NAC module 1 AC failure 24 Remote NAC module 4, output 1 wiring fault 73
Remote NAC module 2 AC failure 25 Remote NAC module 4, output 2 wiring fault 74
Remote NAC module 3 AC failure 26 Remote NAC module 4, output 3 wiring fault 75
Remote NAC module 4 AC failure 27 Remote NAC module 4, output 4 wiring fault 76
NAC 1 shorted wiring 28 Remote NAC module 1, output 1, disabled by user 77
NAC 2 shorted wiring 29 Remote NAC module 1, output 2, disabled by user 78
Remote NAC module 1 ground fault- short 30 Remote NAC module 1, output 3, disabled by user 79
Remote NAC module 2 ground fault- short 31 Remote NAC module 1, output 4, disabled by user 80
Remote NAC module 3 ground fault- short 32 Remote NAC module 2, output 1, disabled by user 81
Remote NAC module 4 ground fault- short 33 Remote NAC module 2, output 2, disabled by user 82
NAC 1 overcurrent 34 Remote NAC module 2, output 3, disabled by user 83
NAC 2 overcurrent 35 Remote NAC module 2, output 4, disabled by user 84
Remote NAC module 1 low battery 36 Remote NAC module 3, output 1 disabled by user 85
Remote NAC module 2 low battery 37 Remote NAC module 3, output 2 disabled by user 86
Remote NAC module 3 low battery 38 Remote NAC module 3, output 3 disabled by user 87
Remote NAC module 4 low battery 39 Remote NAC module 3, output 4 disabled by user 88
Communication path IP #1 fault 40 Remote NAC module 4, output 1 disabled by user 89
Multiplex bus outputs disabled by user 46 Remote NAC module 4, output 2 disabled by user 90
Dialer disabled by user 47 Remote NAC module 4, output 3 disabled by user 91
Relay 1 disabled by user 48 Remote NAC module 4, output 4 disabled by user 92
Relay 2 disabled by user 49 Four zone expander installation fault 93
Relay 3 disabled by user 50 MUX (DS9341) expander installation fault 94
Remote relay module 1 disabled by user 51 Communication path IP #2 fault 95