FPD-7024 | Operation and Installation Guide | 5.0 Control Panel Programming
68
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
Pressing [9] retrieves the second digit options (point numbers). The following window appears:
4/2 ZONE RPT
1- POINT 1 D2
2- POINT 2 D2
3- POINT 3 D2
4- POINT 4 D2
5- POINT 5 D2
6- POINT 6 D2
7- POINT 7 D2
8- POINT 8 D2
9- MORE
Press the number key that corresponds with your selection of event type (D2 stands for digit 2). Press
[#/Enter].
Pressing [9] retrieves additional second digit options (point numbers). The following window appears:
4/2 ZONE RPT
1- POINT 9 D2
2- POINT 10 D2
3- RETURN TO D1
Press the number key that corresponds to your selection. A window based on your previous selection
allowing entry of hex digits appears:
FIRE ALARM D1 ( )
0 THRU 9
<HISTORY>: A
<TEST>: B
<DISABLE>: C
<DRILL>: D
<SILENCE>: E
<RESET>: F
Enter the digit that corresponds to the selected condition by pressing a number key or one of the special keys
if a hex character is needed. Press [#/Enter] and the previous display appears.
5.7.2 4/2 Report Codes
4/2 Report Codes apply to system conditions but only when 3/1 or 4/2 format is selected. Two digits can be
programmed to be sent for each condition. The conditions that can be programmed are:
• System in test, system in test restore: sent for walk test operations
• Silence: sent when the silence key is pressed
• Fire drill, fire drill restore: sent for fire drill operations
• Open reset report: sent when the reset key is pressed
• Low battery, low battery restore, AC failure, AC failure restore: sent for power problems
• Test report: sent for manual or automatic communicator tests
• Off normal at test: sent if the panel is off-normal at the automatic test time
• Phone trouble, restore: sent for phone line problems
• System trouble, restore: sent for general system problems