FPD-7024 | Operation and Installation Guide | Appendix C: Reporting Summary for Fire Communicator
86
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
Appendix C: Reporting Summary for Fire Communicator
Table 29: Reporting Summary for Fire Communicator
Default Values Alternate Default
Report Ind
ex
4/2 digit
1
4/2 digit
2
4/2 digit
1
4/2 digit
2
3/1 BFSK SIA Contact ID Modem IIIa
2
POINT FIRE ALARM 0 0 p 0 p 0 z0 FAz 1 110 00 zzz refer to Table 28
POINT WATERFLOW ALARM 1 0 p 0 p 0 z0 SAz 1 113 00 zzz refer to Table 28
POINT SUPERVISORY ALARM 2 0 p 0 p 0 z0 SSz 1 200 00 zzz refer to Table 28
POINT MONITOR ALARM 3 0 p 0 p 0 z0 UAz 1 140 00 zzz refer to Table 28
POINT FIRE TROUBLE 4 6 p 6 p 6 Fz FTz 1 373 00 zzz refer to Table 28
POINT WATERFLOW TROUBLE 5 (see #4) p (see #4) p (see #4) Fz STz 1 373 00 zzz refer to Table 28
POINT SUPERVISORY TROUBLE 6 (see #4) p (see #4) p (see #4) Fz STz 1 373 00 zzz refer to Table 28
POINT MONITOR TROUBLE 7 (see #4) p (see #4) p (see #4) Fz UTz 1 373 00 zzz refer to Table 28
POINT FIRE DIRTY 8 (see #4) p (see #4) p (see #4) Fz FSz 1 385 00 zzz refer to Table 28
POINT WATERFLOW DIRTY 9 (see #4) p (see #4) p (see #4) Fz FSz 1 385 00 zzz refer to Table 28
POINT SUPERVISORY DIRTY 10 (see #4) p (see #4) p (see #4) Fz FSz 1 385 00 zzz refer to Table 28
POINT MONITOR DIRTY 11 (see #4) p (see #4) p (see #4) Fz UTz 1 373 00 zzz refer to Table 28
POINT FIRE DISABLE 12 B p 5 p B Fz FBz 1 571 00 zzz refer to Table 28
POINT WATERFLOW DISABLE 13 (see #12) p (see #12) p (see #12) Fz FBz 1 571 00 zzz refer to Table 28
POINT SUPERVISORY DISABLE 14 (see #12) p (see #12) p (see #12) Fz FBz 1 571 00 zzz refer to Table 28
POINT MONITOR DISABLE 15 (see #12) p (see #12) p (see #12) Fz FBz 1 571 00 zzz refer to Table 28
POINT FIRE ALARM RESTORE 16 3 p 2 p 3 Ez FRz 3 110 00 zzz refer to Table 28
POINT WATERFLOW RESTORE 17 (see #16) p (see #16) p (see #16) Ez SHz 3 113 00 zzz refer to Table 28
POINT SUPERVISORY RESTORE 18 (see #16) p (see #16) p (see #16) Ez SRz 3 200 00 zzz refer to Table 28
POINT MONITOR RESTORE 19 (see #16) p (see #16) p (see #16) Ez URz 3 140 00 zzz refer to Table 28
POINT FIRE TROUBLE RESTORE 20 3 p 7 p 3 Ez FJz 3 373 00 zzz refer to Table 28
POINT WATERFLOW TROUBLE RESTORE 21 (see #20) p (see #20) p (see #20) Ez SJz 3 373 00 zzz refer to Table 28
POINT SUPERVISORY TROUBLE RESTORE 22 (see #20) p (see #20) p (see #20) Ez SJz 3 373 00 zzz refer to Table 28
POINT MONITOR TROUBLE RESTORE 23 (see #20) p (see #20) p (see #20) Ez UJz 3 373 00 zzz refer to Table 28
POINT FIRE DIRTY RESTORE 24 (see #20) p (see #20) p (see #20) Ez FJz 3 385 00 zzz refer to Table 28
POINT WATERFLOW DIRTY RESTORE 25 (see #20) p (see #20) p (see #20) Ez FJz 3 385 00 zzz refer to Table 28
POINT SUPERVISORY DIRTY RESTORE 26 (see #20) p (see #20) p (see #20) Ez FJz 3 385 00 zzz refer to Table 28
POINT MONITOR DIRTY RESTORE 27 (see #20) p (see #20) p (see #20) Ez UJz 3 373 00 zzz refer to Table 28
POINT FIRE DISABLE RESTORE 28 3 p 2 p A Ez FHz 3 571 00 zzz refer to Table 28
POINT WATERFLOW DISABLE RESTORE 29 (see #28) p (see #28) p (see #28) Ez FHz 3 571 00 zzz refer to Table 28
POINT SUPERVISORY DISABLE RESTORE 30 (see #28) p (see #28) p (see #28) Ez FHz 3 571 00 zzz refer to Table 28
POINT MONITOR DISABLE RESTORE 31 (see #28) p (see #28) p (see #28) Ez FHz 3 571 00 zzz refer to Table 28
SYSTEM IN TEST 40 F 1 3 3 F FD TS0 1 607 00 000 refer to Table 28
SYSTEM IN TEST RESTORE 41 E 1 3 7 E ED TE0 3 607 00 000 refer to Table 28
SILENCE 42 9 F 9 F 9 FD KBuu 1 400 00 uuu refer to Table 28
Table 29: Reporting Summary for Fire Communicator