FPD-7024 | Operation and Installation Guide | Appendix C: Reporting Summary for Fire Communicator
88
Bosch Security Systems, Inc. | 1/10 | F01U008458-03
When the Modem IIIa
2
reporting format is used with a Bosch Security Systems, Inc. receiver, refer to Table 30
for information about the receiver output.
Table 30: Modem IIIa
2
Reporting
Report Index Receiver Output
POINT FIRE ALARM 0
dd/dd tt:tt ql ACCT aaaa FIRE ALARM
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW ALARM 1
dd/dd tt:tt ql ACCT aaaa FIRE ALARM
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY ALARM 2
dd/dd tt:tt ql ACCT aaaa FIRE SUPRVISION
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR ALARM 3
dd/dd tt:tt ql ACCT aaaa FIRE ALARM
+++ ACCT aaaa AREA=1 POINT=zzz
POINT FIRE TROUBLE 4
dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW TROUBLE 5
dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY TROUBLE 6
dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR TROUBLE 7
dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE
+++ ACCT aaaa AREA=0 POINT=zzz
POINT FIRE DIRTY 8
dd/dd tt:tt ql ACCT aaaa ANALOG SERVICE
+++ ACCT aaaa AREA=0 POINT=zzz
POINT WATERFLOW DIRTY 9
dd/dd tt:tt ql ACCT aaaa ANALOG SERVICE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT SUPERVISORY DIRTY 10
dd/dd tt:tt ql ACCT aaaa ANALOG SERVICE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT MONITOR DIRTY 11
dd/dd tt:tt ql ACCT aaaa FIRE TROUBLE
+++ ACCT aaaa AREA=1 POINT=zzz
POINT FIRE DISABLE 12
dd/dd tt:tt ql ACCT aaaa COMMAND BYPASS
+++ ACCT aaaa AREA=1 ID=uuu POINT=zzz
POINT WATERFLOW DISABLE 13
dd/dd tt:tt ql ACCT aaaa COMMAND BYPASS
+++ ACCT aaaa AREA=1 ID=uuu POINT=zzz
POINT SUPERVISORY DISABLE 14
dd/dd tt:tt ql ACCT aaaa COMMAND BYPASS
+++ ACCT aaaa AREA=1 ID=uuu POINT=zzz
POINT MONITOR DISABLE 15
dd/dd tt:tt ql ACCT aaaa COMMAND BYPASS
+++ ACCT aaaa AREA=1 ID=uuu POINT=zzz
POINT FIRE ALARM RESTORE 16
dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz
POINT WATERFLOW RESTORE 17
dd/dd tt:tt ql ACCT aaaa FIRE ALM RESTOR
+++ ACCT aaaa AREA=1 POINT=zzz