4.7 Remote Programming
The system operates during remote programming
so that new alarms end the remote programming
session and report normally. Using the keypads to
perform other functions during remote
programming (such as tests and disables) can
cause remote programming to disconnect or other
unexpected operations. Avoid downloading
programming changes that cause alarms, because
the session disconnects as soon as the alarm
occurs, before the session completes. To indicate
that the system is in a special operating mode with
user input inhibited (but alarm monitoring
continuing), the system indicates SYSTEM
TROUBLE, RMT PRG ACTIVE during remote
programming. Sounders do not activate during this
mode, but other outputs programmed for Zone 62,
general system trouble, do activate.
Trouble conditions that occur during a remote
programming session are not annunciated at the
control panel until the remote programming session
ends. These conditions are available in the remote
programmer diagnostic displays during the
session. Alarm conditions terminate remote
programming and are shown immediately.
When remote programming is disabled, you can
still connect to the control panel for diagnostics and
view the existing programming (except PIN
numbers). To actually change programming,
enable remote programming.
To enable remote programming, refer to the
following programming items:
0-3-7 Remote Programming (Section 5.3.5
Remote Programming on page 47)
0-6-1 Computer Phone (Section 5.6.1 Phone
Numbers/IP Addresses on page 58)
0-6-1 Account Number 1 (Account Numbers on
page 62)
0-6-2 Dialing Type (Dialing Type on page 64)
0-6-4 Ring Count (Section 5.6.4 Ring Count on
page 66.
0-6-6 Machine Bypass (Section 5.6.6 Machine
Bypass on page 66)
An access code with maximum authority (1) is
needed to begin remote programming from the
panel.