Table 7: Alarm Load Battery Size (Ah)
Alarm Load Battery Size Chart Capacity
Required for 5
Minutes
Capacity
Required for 10
Minutes
Capacity
Required for 15
Minutes
Capacity
Required for 30
Minutes
Capacity
Required for 45
Minutes
Grand Total Standby Existing
250 to 500 mA 0.1 0.1 0.2 0.3 0.5
501 to 999 mA 0.1 0.2 0.3 0.6 0.9
1.0 to 1.5 A 0.2 0.3 0.5 0.9 1.4
1.6 to 2.0 A 0.2 0.4 0.6 1.2 1.8
2.1 to 2.5 A 0.3 0.5 0.8 1.5 2.3
2.6 to 3.0 A 0.3 0.6 0.9 1.8 2.7
3.1 to 3.5 A 0.4 0.7 1.1 2.1 3.2
3.6 to 4.0 A 0.4 0.8 1.2 2.4 3.6