Verification
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
This feature resets the detector once to determine if the alarm recurs before annunciating or sending a signal.
The total delay introduced by this feature is equal to the smoke power reset time plus five seconds. Alarm
verification cannot be selected for points that are configured as WATERFLOW or SUPERVISORY types.
Enter the point number you wish to verify and press [#/Enter]. The display scrolls through the PROG INPUT
options.
Press [3] to select VERIFICATION. The following window appears:
ALARM VERIF (ZZZ)
____:YES(1)NO(0)
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press either [1] to verify or [0/Prog] to not verify. The previous window appears.
Latching
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
If a zone is non-latching, the system resets the alarm status automatically (but does not reset smoke power)
when the input restores to the standby condition. Otherwise, the system must be manually reset. Refer to
Table 15 on page 32.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [4/] to select LATCHING. The following window appears:
LATCHING? ZZZ
____:YES(1)NO(0)
ZZZ indicates the point being programmed. The existing setting is shown on the second line.
Press the number key that corresponds to your selection. Select YES for alarm.
The previous window appears.
Point Description
Shortcut: 0-PROG, 4-PROG INPUTS, 1-POINT NUMBER
For this feature, use the numeric keys to enter alphanumeric information to identify each input (such as
initiating circuit). The system allows one 16-character description per input.
Enter the point number you wish to program and press [#/Enter]. The display scrolls through the PROG
INPUT options.
Press [5] to select DESCRIPTION. The following window appears:
PNT DSCRPTN ZZZ:
____________________
Enter the description using the numeric, [Silence] and [History] keys, then press [#/Enter] to save the
description.