EN | 53FPT-DACT | Operation & Installation Guide |
1/05 | F01U002505B
Appendix D
Items crossed out are not currently
supported.
Report Steering
Non-SUP Alarm: Phone 2 Backup
Supervisory Alarm: Phone 2 Backup
Alarm Restor, Reset: Phone 2 Backup
Supervisory Restore: Phone 2 Backup
Tests: Phone 2 Backup
Trbl, Trbl Restore: Phone 2 Backup
Line Control
Line 1 Dialing Type: Tone/Pulse
Line 2 Dialing Type: Tone/Pulse
Line 1 Monitor Line: Yes
Line 2 Monitor Line: Yes
Line 1 Wait Dial Tone: Yes
Line 2 Wait Dial Tone: Yes
ACK WAIT TIME: 45 sec
Program Formats (4/2 Point Rpt)
Fire Alarm Digit 1: 0
Fire Rstrl Digit 1: 3
Waterflow Digit 1: 0
Supervise Digit 1: 0
Trouble Digit 1: 6
Trbl Rstrl Digit 1: 3
Disable Digit 1: B
Disable Rtrl Digit 1: 3
Monitor Digit 1: 0
Zone 1 Digit 1: 1
Zone 2 Digit 1: 2
Zone 3 Digit 1: 3
Zone 4 Digit 1: 4
Zone 5 Digit 1: 5
Program Formats (4/2 Rpt Codes Group 1)
System in Tst: F1
Sys Tst Rstrl: E1
Silence: 9F
Fire Drill: F2
Fire Drill Rstl: E2
Open Reset: 9F
Low Batt: F9
Low Batt Rstrl: E9
AC Fail: F8
Appendix D: Programming Defaults
This appendix contains a list of all the programming
defaults for the FPT-DACT. Use the FPT-DACT Program
Record Sheet (P/N: 46086) to record programming
entries.
Program Time
System Date
*
: 01 01 00
System Time
*
: 0000
* Once the user enters the system date and time, resetting
the FPT-DACT to its default settings does not reset the
system date and time. The system time can be corrupted
if the power fails for more than 5 min.
Auto Test
Auto Test Time: 0400
Auto Test Frequency: 24 h
Daylight Savings: No
Timers
AC Fail Delay: 6 h
Display Rate: 1 second
Program Inputs (Configure)
Point 1: Waterflow
Point 2: Fire
Point 3: Supervisory
Point 4: Fire
Point 5: Fire
Program Inputs (Supervised)
Point 1: No
Point 2: No
Point 3: No
Point 4: No
Point 5: No
Configure Relay: Release on Trouble
Program Accounts
Account #1: 0000
Account #2: 0000
Phone Numbers
Phone #1: ?????????
Phone #2: ?????????
Phone #3: ?????????
Phone Control
Phone #1 Format: SIA 300
Phone #2 Format: SIA 300
Phone #1 Tone: 19D, 14A, 10PS
Phone #2 Tone: 19D, 14A, 10PS
Phone #1 Text: No
Phone #2 Text: No