EN | 53FPT-DACT | Operation & Installation Guide |
1/05 | F01U002505B
Appendix D
Items crossed out are not currently
supported.
Report Steering
• Non-SUP Alarm: Phone 2 Backup
• Supervisory Alarm: Phone 2 Backup
• Alarm Restor, Reset: Phone 2 Backup
• Supervisory Restore: Phone 2 Backup
• Tests: Phone 2 Backup
• Trbl, Trbl Restore: Phone 2 Backup
Line Control
• Line 1 Dialing Type: Tone/Pulse
• Line 2 Dialing Type: Tone/Pulse
• Line 1 Monitor Line: Yes
• Line 2 Monitor Line: Yes
• Line 1 Wait Dial Tone: Yes
• Line 2 Wait Dial Tone: Yes
ACK WAIT TIME: 45 sec
Program Formats (4/2 Point Rpt)
• Fire Alarm Digit 1: 0
• Fire Rstrl Digit 1: 3
• Waterflow Digit 1: 0
• Supervise Digit 1: 0
• Trouble Digit 1: 6
• Trbl Rstrl Digit 1: 3
• Disable Digit 1: B
• Disable Rtrl Digit 1: 3
• Monitor Digit 1: 0
• Zone 1 Digit 1: 1
• Zone 2 Digit 1: 2
• Zone 3 Digit 1: 3
• Zone 4 Digit 1: 4
• Zone 5 Digit 1: 5
Program Formats (4/2 Rpt Codes Group 1)
• System in Tst: F1
• Sys Tst Rstrl: E1
• Silence: 9F
• Fire Drill: F2
• Fire Drill Rstl: E2
• Open Reset: 9F
• Low Batt: F9
• Low Batt Rstrl: E9
• AC Fail: F8
Appendix D: Programming Defaults
This appendix contains a list of all the programming
defaults for the FPT-DACT. Use the FPT-DACT Program
Record Sheet (P/N: 46086) to record programming
entries.
Program Time
• System Date
*
: 01 01 00
• System Time
*
: 0000
* Once the user enters the system date and time, resetting
the FPT-DACT to its default settings does not reset the
system date and time. The system time can be corrupted
if the power fails for more than 5 min.
Auto Test
• Auto Test Time: 0400
• Auto Test Frequency: 24 h
Daylight Savings: No
Timers
• AC Fail Delay: 6 h
• Display Rate: 1 second
Program Inputs (Configure)
• Point 1: Waterflow
• Point 2: Fire
• Point 3: Supervisory
• Point 4: Fire
• Point 5: Fire
Program Inputs (Supervised)
• Point 1: No
• Point 2: No
• Point 3: No
• Point 4: No
• Point 5: No
Configure Relay: Release on Trouble
Program Accounts
• Account #1: 0000
• Account #2: 0000
Phone Numbers
• Phone #1: ?????????
• Phone #2: ?????????
• Phone #3: ?????????
Phone Control
• Phone #1 Format: SIA 300
• Phone #2 Format: SIA 300
• Phone #1 Tone: 19D, 14A, 10PS
• Phone #2 Tone: 19D, 14A, 10PS
• Phone #1 Text: No
• Phone #2 Text: No