EN | 49FPT-DACT | Operation & Installation Guide |
1/05 | F01U002505B
Appendix C
Appendix C: Fire Communicator Report Summary
Table 11: Reporting Summaries
Point-Related Events
Report
Description
SIA
Code
SIA
Description
Contact ID
Code
Contact ID
Description
4/2 Code
Default
Values
Modem IIIa
2
Description
Point Fire Alarm FA pppp Fire Alarm 1 110 aa ppp Fire Alarm 0P Fire Alarm Point = ppp
Point Waterflow
Alarm
SA pppp
Sprinkler
Alarm
1 113 aa ppp Waterflow 0P Fire Alarm Point = ppp
Point
Supervisory
Alarm
SS pppp
Sprinkler
Supervisory
1 200 aa ppp
Fire
Supervisory
0P
Fire Supervision
Point = ppp
Point Monitor
Alarm
UA pppp
Untyped Zone
Alarm
1 140 aa ppp General Alarm 0P Alarm Point = ppp
Point Fire
Trouble
FT pppp Fire Trouble 1 373 aa ppp Fire Trouble 6P
Fire Trouble
Point = ppp
Point Waterflow
Trouble
ST pppp
Sprinkler
Trouble
1 373 aa ppp Fire Trouble 6P
Fire Trouble
Point = ppp
Point
Supervisory
Trouble
ST pppp
Sprinkler
Trouble
1 373 aa ppp Fire Trouble 6P
Fire Trouble
Point = ppp
Point Monitor
Trouble
UT pppp
Untyped Zone
Trouble
1 373 aa ppp Fire Trouble 6P Trouble Point = ppp
Point Fire Alarm
Restore
FR pppp Fire Restoral 3 110 aa ppp Fire Alarm 3P
Fire Restoral
Point = ppp
Point Waterflow
Restore
SH pppp
Sprinkler
Alarm Restore
3 113 aa ppp Waterflow 3P
Fire Restoral
Point = ppp
Point
Supervisory
Restore
SR pppp
Sprinkler
Restoral
3 200 aa ppp
Fire
Supervisory
3P
Fire Restoral
Point = ppp
Point Monitor
Restore
UR pppp
Untyped Zone
Restoral
3 140 aa ppp General Alarm 3P
Restoral From Alarm
Point = ppp
Point Fire
Trouble Restore
FJ pppp
Fire Trouble
Restore
3 373 aa ppp Fire Trouble 3P
Fire Trouble Restoral
Point = ppp
Point Waterflow
Trouble Restore
SJ pppp
Sprinkler
Trouble
Restore
3 373 aa ppp Fire Trouble 3P
Fire Trouble Restoral
Point = ppp
Point
Supervisory
Trouble Restore
SJ pppp
Sprinkler
Trouble
Restore
3 373 aa ppp Fire Trouble 3P
Fire Trouble Restoral
Point = ppp
Point Monitor
Trouble Restore
UJ pppp
Untyped
Trouble
Restore
3 373 aa ppp Fire Trouble 3P Restoral Point = ppp
Open Reset OR iii
Disarm From
Alarm
1 401 aa iii O/C By User 9F Sensor Reset ID = iii
Low Battery YT
System
Battery
Trouble
1 302 aa 000
Low System
Battery
F9 Battery Low
Low Battery
Restore
YR
System
Battery
Restoral
3 302 aa 000
Low System
Battery
E9 Battery Restoral
AC Fail AT AC Trouble 1 301 aa 000 AC Loss F8 AC Fail
AC Fail Restore AR AC Restoral 3 301 aa 000 AC Loss E8 AC Restoral
Auto Test RP
Automatic
Test
1 602 aa 000
Periodic Test
Report
EE
Test Report Non
Expanded