Electrostatic discharge
ESD resistance acc. to DIN EN 61131-2
Test voltage
Criterion B
6 kV for contact discharge
8 kV for air discharge
The vibration stress specifications assume the use of industrial-suited RJ-45 plug connec-
tions. The "Industrial RJ-45 plug" of the company Yamaichi is recommended (Y-Con-
Plug-41). The cables are available as accessories (RKB0020). To avoid vibration, secure
the cables using a short distance (< 20 cm). The USB interfaces XF30 and XF31 may only
be used up to a vibration stress of 1 g.
Tab. 6-1: Ambient conditions
Failure of the product due to contaminated air
NOTICE
The ambient air must not contain acids, alkaline solutions, corrosive agents,
salts, metal vapors and other electrically conductive contaminants in high
concentrations
The devices to be installed into the housing and installation compartments
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
The device shall be provided in a suitable fire enclosure in the end-use appli-
cation.
Defective product due to gases jeopardizing
functions
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
2
)
and hydrogen suphide (H
2
S)). The product is not resistant against these gases.
Failure of the product due to overheating
NOTICE
To avoid overheating and to ensure a smooth operation of the product according
to the minimum distances specified in chapter 10.1 "Installation notes" on page
16, air has to circulate.
This is a product that corresponds to the limit values of the emitted
interference of class A (industrial environments), but not of class B
(residential area and small enterprises).
When using the product in residential areas or small enterprises, the
operator has to take actions to prevent radio interferences (also re-
fer to DIN EN 55022).