5.5 End clamp
Ordering code Part number Description
SUP-M01-ENDHALTER R911170685 2 pieces of snap-on end brackets for 35 mm NS 35/7.5
or NS 35/15 carrier plate; width: 9.5 mm
Tab. 5-5: End clamp
5.6 Wear parts
There are no wear parts in the control IndraControl XM4.
6 Ambient conditions
Ambient temperature during operation without fan Up to 2,000 m: -25 °C to +50 °C
2,000 m to 3,000 m: max. +45 °C
Ambient temperature during storage and transport -25°C to +70°C
Air pressure 55 kPa to 106 kPa (up to 4,500 m above sea level)
Air humidity 5 % to 95 % acc. to DIN EN 61131-2, no conden-
sation
Degree of protection IP20 acc. to DIN EN 60 529
Protection class III, DIN EN 61010-2-201
Overvoltage category 2
Contamination level 2, no condensation allowed
Mechanical tests
Vibration resistance acc. to DIN EN 60068-2-6
①
Oscillations, sinusoidal in all three axes
5 Hz - 8.4 Hz with 3.5 mm amplitude
8.4 Hz -150 Hz with 1 g peak acceleration
Shock test acc. to DIN EN 60068-2-27 Shock stress: Shock resistance in all three axes,
11 ms semi-sinusoidal 15 g
Broadband noise acc. to DIN EN 60068-2-64
20-500 Hz with 1.22 g rms
1)
per axis
1)
Root Mean Square
IndraControl XM42 Controls 7/65
Ambient conditions
R911345566_Edition 03 Bosch Rexroth AG