LED Function Color Status
D Delete network configuration Red Function is selected, pro-
cessed
Flashing red Confirm selection
E Start First Touch Red Function is selected, pro-
cessed
Flashing red Confirm selection
Green First Touch running
Tab. 12-4: LED states
The LED states described are only valid together with the initial firm-
ware.
For more information on the LED states in operation, refer to the
functional description of the respective control system (IndraMotion
MLC, IndraMotion MTX).
12.2.3 Starting and opening the initial firmware
No system firmware is yet installed on the XM4x control upon delivery. Apply the
supply voltage and the control starts the initial firmware and the commissioning
tool "IndraControl First Touch" automatically. To manually execute the basic
functions of the initial firmware, press the "Reset" button when switching on the
24 V supply voltage until the LEDs DIA3 and DIA4 flash alternatingly in red. Sub-
sequently, one of the following functions can be opened via a menu structure:
Menu item number
Functions LED Color
1 Start First Touch E Red
2 Start First Touch, delete network configuration E
D
Red
Red
3 Start First Touch, delete network configuration, reset user
name and password
E
D
BT
Red
Red
Red
4 Start First Touch, delete network configuration, reset user
name and password, delete files, restore state upon delivery
E
D
BT
ERR
Red
Red
Red
Red
Tab. 12-5: Menu items of the initial firmware
If the function was executed successfully, the LED "E" changes from
red to green after some seconds.
The control must not be switched off during this time.