① Grounding screw
Fig. 10-16: Position of the grounding screw
Potential equalization
Potential equalization acc. to DIN VDE 0100 part 540 has to be provided be-
tween the system parts and the voltage supply.
10.7.5 Shielding
Control failure due to insufficient shielding
Provide sufficient shielding.
The shielding reduces any effects of interferences on the system.
Observe the following when shielding:
● Fasten the shielding as extensively as possible
● Ensure proper contact between connector and terminal
● Avoid damaging or squeezing conductors
● Note the wire specifications when connecting the shielding
● Shield the closest possible to the signal terminal points
Route all power cables and data cables in separate cable channels.
10.8 Battery
A battery is included in the device upon delivery. Battery name: Lithi-
um battery 3.0 V CR1632 (120 mAH), manufacturer: Renata.
30/65
Mounting, demounting and electric installation
IndraControl XM42 Controls
Bosch Rexroth AG R911345566_Edition 03