In operation Transport Storage
Mechanical
strength
Max. Vibration:
Frequency range:
10 Hz to 150 Hz
Excursion:
0.75 mm at 10 Hz to 57 Hz
Acceleration:
1 g at 57 Hz to 150 Hz
Acc. to EN 60068-2-6
Max. Shock:
15 g 11 ms
Acc. to EN 60068-2-27
Max. Shock:
15 g 11 ms
Acc. to EN 60068-2-27
Contamination
level acc. to EN
60664-1
2 2 2
Overvoltage
category acc.
to EN 60664-1
2 – –
Tab. 6-1: Ambient conditions
Defective product due to gases jeopardizing
functions
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
2
)
and hydrogen suphide (H
2
S)). The product is not resistant against these gases.
The device is not resistant to gas jeopardizing the function [sulphur
dioxide (SO
2
), hydrogen sulphide (H
2
S)].
Failure of the product due to contaminated air
● The ambient air must not contain acids, alkaline solutions, corrosive agents,
salts, metal vapors and other electrically conductive contaminants in high
concentrations
● The devices to be installed into the housing and installation compartments
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
● The device shall be provided in a suitable fire enclosure in the end-use
application.
IndraControl VPB 40.4
Bosch Rexroth AG
Ambient conditions
DOK-MLC***-INDRACTRLV4-IT02-EN-P
9/87