Pin Labeling Function
1 + Supply voltage 24 V
2 0 V supply voltage
3 U Supply voltage available in front of the UPS (see chapter 10.3.2
"Connecting a UPS" on page 33)
Destruction of the control cabinet PC (fire
hazard) due to polarity reversal of the
connection at the X10 plug without additional
external protection
NOTICE
Ensure that the polarity at the X10 plug and the dimensioning of the fuse are
correct.
Danger without safe separation!
WARNING
The 24 V DC input voltage must comply with the requirements of the "safe
separation"!
Plug and remove the plug connection only if there is no voltage!
Conductors Cross-section
Conductor cross-section inflexible, max.
10 mm
2
Conductor cross-section inflexible, recommended
2.5 mm
2
Conductor cross-section flexible, max.
6 mm
2
Conductor cross-section flexible, recommended
2.5 mm
2
Conductor cross-section flexible with core end sleeves without plastic sleeve,
max.
6 mm
2
Conductor cross-section flexible with core end sleeves without plastic sleeve,
recommended
2.5 mm
2
Conductor cross-section flexible with core end sleeves with plastic sleeve, max.
4 mm
2
Conductor cross-section flexible with core end sleeves with plastic sleeve,
recommended
2.5 mm
2
Conductor cross-section AWG/kcmil, max. 8
Conductor cross-section AWG/kcmil, recommended 13
Tab. 9-1: Conductor cross-sections permitted for the spring terminal at X10
9.3 Reset button
When the "Reset" button is pressed, the mainboard is restarted immediately.
IndraControl VPB 40.4
Bosch Rexroth AG
Interfaces
DOK-MLC***-INDRACTRLV4-IT02-EN-P