5-18 Electrical installation REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
Connecting the operator panel
The operator panel can either be inserted directly at connector X11 can
be connected using the above specified cable.
Connecting a PC
The cable to connect a PC must have the following configuration:
Drive converter
X11
RxD
TxD
GND
3
2
5
PC
TxD
RxD
GND
Shield connection
3
2
5
Fig. 5-13: Connecting cable for the PC
Alternatively, the operator panel cable can be used.
The following settings must be observed:
Can be set with P0499: 1200, 2400, 4800, 9600 (factory setting), 19200,
38400, 57600, 76800 baud
8
Even
1
USS protocol, 4/6 words
5.8 Standard RS485 interface (X12)
The RS485 interface supports the USS protocol,, which is used to control
the drive converter via a PLC. The USS protocol (Universal S
erial Inter-
face protocol) defines an access technique according to the master-slave
principle for communications via a serial bus.
Drive converter
X12
TxD+ /RxD+
TxD- / RxD-
1
2
Control
TxD+ /RxD+
TxD- / RxD-
Shield connection
to the next
slave
Fig. 5-14: Connecting the standard interface
When using this interface, it should be noted, that the same interface
configuration is set for every bus node.
Exception: "SS1 slave address" - in this case, every bus node has its
own address.
Bus termination
The last node of a bus system must terminate the bus to protect against
the influence of noise. The bus termination is switched-in using a switch
on the control card (refer to Section 5.6, Control terminals).
Baud rate:
Data bits:
Parity:
Stop bits:
Protocol type: