REFUspeed RS51 Basic parameterization 7-23
DOK-RD500*-RS51*******-IB02-EN-P
Serial communications
Sub-menu to set standard RS485 interfaces.
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0500 SI1 protocol X12 The serial interface 1 (SS1) is an RS485 interface
(connection X12).
0 = No protocol
1= USS4/2words
2= USS4/6words
3= USS0/2words
4= USS0/6words
5= USS4/0words
USS 4/6 words
0 ... 5
2
0501 SI1 baud rate X12
0 = 1200 baud
1 = 2400 baud
2 = 4800 baud
3 = 9600 baud
4 = 19200 baud
5 = 38400 baud
6 = 76800 baud
9600 baud
0 ... 6
2
0502 SI1 parity X12
0 = No parity
1= ODD
2 = EVEN
Even
0 ... 2
2
0503 SI1 stop bits X12
1or2stopbitscanbeset.
1
1 ... 2
2
0504 SI1 slave address
The drive converter address can be set between 0 and
31 for the RS485 bus. Caution: There must be no two
identical addresses on the bus (each station/node
must have ist own unique address)!
0
0 ... 31
2
0505 SI1 Rx watchdog
0 = No reaction
1= Warning
2 = Fault
Fault
0 ... 2
2
0506 SI1 Rx timeout
Timeout (monitoring) time for the standard SS1 inter-
face. If this interface does not receive an error-free
protocol within this time, then the response, selected
in P0505 is initiated.
0.1 s
0.1 ... 60.0 s
2