7-22 Basic parameterization REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0064 Parameteriz. level
0 = basic parameterization: The operator has
access to the pre-defined parameters of the
basic parameterization, menu-prompted or
via the numerical list.
1 = free parameterization: The operator can
access all of the parameters associated
with the free parameterization.
Caution: Data can be lost when changing the
parameterizing modes! Please carefully read the Sec-
tion, 1.4 Working with basic parameterization and the
free parameterization in the Manual, Function charts
and parameter list.
Basic parameter-
ization:
0/1
23
0037.00 Display, lines 1,2,3
Selects the operating display for line 1.
0 = status (drive status message)
1 = actual speed (electrical)
2 = output effective current
3 = output current (actual apparent current)
4 = output voltage
5 = DC link voltage
6 = frequency actual value
7 = frequency setpoint
8 = P act (actual apparent power)
9 = P active (active power which the motor takes)
f actual
0 ... 9
0
0037.01 Display, lines 1,2,3
Selects the operating display for line 2.
As for parameter 0037.00.
Frequency setpoint
0 ... 9
0
0037.02 Display, lines 1,2,3
Selects the operating display for line 3.
As for parameter 0037.00.
Status
0 ... 9
0
0734 Display contrast
Sets the contrast for the operator panel display
11
10 ... 20
0
0072 Source parameter
Specifies from which source parameters can be set.
0 = Keypad, PC (RS232),
1 = Bus SS1,
2 = Bus SS2,
3 = Bus SS4,
4 = All busses,
5 = Bus SS6
Keypad, PC
0 ... 5
2