4-2 Mounting REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
4.2 Mounting, drives sizes J to M
The REFUdrive 500 drives, sizes J to M are module and are designed
for installation in cabinets.
The drive units have mechanical grid dimensions of 22.5 mm. Several
drive units can be mounted next to one another without any intermedi-
ate space when using mounting rails with threaded holes with the di-
mension grid (also refer to the mounting example).
The drives must be mounted vertically onto a flat surface.
A minimum clearance of 100 mm above and below the drives must be
maintained to ensure an unrestricted cooling airflow.
When mounted in cabinets, the cooling airflow requirement of the in-
stalled drives must be calculated and the cabinet ventilation appropri-
ately dimensioned.
The mounting bolts are specified in the drilling templates of the dimen-
sion drawings.
Minimum clearance
Cooling air
Hot discharged air
100 mm
Minimum clearance
for cooling
100 mm
Minimum clearance
for cooling
Fig. 4-2: Minimum clearance for cooling