7-6 Basic parameterization REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
t
0 %
-100%
100%
Setpoint
RFG output
Ramp-up
time
Ramp-
down
time
Direction of
rotation reversal
Ramp-up
time
Ramp-
down
time
Fig. 7-3: Up and down ramps
7.4 Guided parameterization
Drive control / setpoints
Pa-
rameter
No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0870 On/off for NORMAL
Enters On/off for NORMAL operation
0 = Term. steady-st. (steady-st.
corr. to a switch function)
1 = T. stat.+OP(T=terminals
OP=operator panel)
2 = T. stat.+PC (PC w/ RE
FUwin via service-
interface)
3 = T. stat.+bus SS1
(SS = serial interface)
4 = T. stat.+bus SS2 (if
available)
5 = T. stat.+bus SS4 (if
available)
6 = T. dyn. (OFF always)
(dyn.=dynamic)
7 = OP dyn. (OFF always)
8 = T. dynamic (dynamic
corr. to a pushbutton funct.)
9 = OP dynamic
10 = OP static
11 = T. stat.+bus SS6
Terminal dynamic
0...11
1