REFUspeed RS51 Basic parameterization 7-5
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0778
0390.XX Frequency normali-
zation Reference value for frequency setpoints and actual
values.
This parameter is set to 50 Hz in the factory. To oper-
ate the motor with 50 Hz, a setpoint of 100% must be
entered.
50.00 Hz
15.0 Hz ... P0027
2
0374.XX Current normalization Reference value for current setpoints and actual val-
ues.is set to the value of the drive current in the fac-
tory (P0024).
P0024
0.5 ... 6553.5
2
0072.XX Param. setting Enters from which source the parameter can be set.
0 = Operator panel ,
1 = Bus SS1 ,
2 = Bus SS2 ,
3 = Bus SS4 ,
4 = All buses ,
5 = Bus SS6
Operator panel, PC
0...5
2
0280.YY Ramp-up time Refer to Fig. 5-3: Up and down ramp
Ramp-up time of the ramp-function generator. The
entered time is valid for a setpoint change from 0 % to
100 %.
XX=The index, in which a value can be saved, is se-
lected in parameters P0875, P0876; P0877; P0878,
P0879 or P0880 (function: Setpoint memory, bits 20 ...
23).
5.000 s
0.000 ... 3200.000
s
1
0281.YY Ramp-down time Refer to Fig. 5-3: Up and down ramp
Ramp-down time of the ramp-function generator. The
entered time is valid for a setpoint change normalized
for 100%.
XX=The index, in which a value can be saved, is se-
lected in parameters P0875, P0876; P0877; P0878,
P0879 or P0880 (function: Setpoint memory, bits 20 ...
23).
5.000 s
0.000 ... 3200.000
s
1
1: The motor data of a typical motor are set as factory setting for each
drive output class.
2: This menu item is only displayed, if an induction motor was selected
as motor type.
3: This menu item is only displayed if a synchronous motor was se-
lected as motor type.
XX: The index, shown in the display, is defined by the currently active pa-
rameter set.
YY: The index, shown in the display, is determined by the currently active
setpoint memory.