REFUspeed RS51 Basic parameterization 7-7
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0871 On/off in TEST
Enters On/off for TEST operation.
As for parameter 0870.
OP (Operator
panel) dynamic
0...11
1
0872 Setpoint in NORMAL
Enters the setpoint for NORMAL operation
0 = Motorized potentiometer
1 = Fixed setpoint
2 = Analog input 0..±10V
3 = Analog input 0..+20mA
4 = Analog input 4..+20mA
5 = Opt. an. input 0..±10V (opt.
= optional)
6 = Opt. an. input 0..+20mA
7 = Opt. an. input 4..+20mA
8 = PC (PC with REFUwin via
service interface)
9 = Bus SS1
10 = Bus SS2
11 = Bus SS4
12 = Analog input 2..+10V
13 = Bus SS6
Analog input
0..±10V
0...13
1
0873 Setpoint in TEST
Enters the setpoint for TEST operation
As for parameter 0872.
Motorized potenti-
ometer
0...13
1
0196 Mot. pot. mode Supplementary parameter for motorized potentiome-
ter.
For Start f set, the motorized potentiometer setpoint,
which was set the last after the off command, is ap-
proached.
For Startfmin, the actual f min (P0180.XX) is ap-
proached.
Furthermore, the rate-of-change of the motorized po-
tentiometer can be set using the parameter:
linear = Uniform change
corresponding to the
selected step width
expon. = The rate-of-change
increases the longer that
the button remains pressed
0 = Start f set, linear
1 = Start f min, linear
2 = Start f set, exponential
3 = Start f min, exponential
Start f set, expon.
0 ... 3
1
10195 Mot. pot. step value Supplementary parameter for motorized potentiome-
ter.
The motorized potentiometer rate-of-change is set
using the step width.
0.01
0.01 ... 10.00 Hz
10265.YY Fix value main s/p Supplementary parameter for fixed setpoint.
Parameter P0390 is the reference value for the fre-
quency setpoints and actual values.
P0390 is set to 50 Hz in the factory. This means that
to operate the motor with 50 Hz, a setpoint of 100%
must be entered.
YY = The index which is displayed is determined by
the presently active setpoint memory.
5.00 %
-199.99 ... 199.99
%
LSA Control S.L. www.lsa-control.com comercial@lsa-control.com (+34) 960 62 43 01