7-8 Basic parameterization REFUspeed RS51
DOK-RD500*-RS51*******-IB02-EN-P
Parame-
ter No.:
Name Description / explanation
selectable options
Factory setting
min ... max values
Pass
wor
d
0297.00 Analog input window Supplementary parameter for analog input.
The analog setpoint smoothing is specified in a win-
dow width in %.
For example: Window width = 1 %. A change in the
actual setpoint is only transferred, if a change greater
than 0.99 % of the possible final value is detected at
the analog input.
0.50 %
0.00 ... 20.00 %
1
0200.00 Analog input norm. Supplementary parameter for analog input.
The analog input normalization refers to the frequency
normalization P0390.
100 %
-199.99 ... 199.99
%
2
0202.00 Analog input offs. Supplementary parameter for analog input.
Analog input offset
0.00 %
-199.99 ... 199.99
%
2
0203.00 Analog input sign. Supplementary parameter for analog input.
Analog input signal
0=direct
1 = absolute value
2=inverted
3 = absolute value, inverted
Direct
0 ... 3
2
0204.00 Analog input filtr. Supplementary parameter for analog input.
Analog input, filter time to smooth the analog signal.
2ms
0 ... 10000 ms
2
0564.nn Reaction on I < 4mA Supplementary parameter for analog input 4...+20
mA.
Response for I<4mA
0 = no reaction
1=warning
2 = fault
nn = 00 for STANDARD mode
nn = 01 for TEST
Warning
0 ... 2
2
0179.YY V/f character. Fmax
YY = The index which is displayed is determined by
the currently active setpoint memory.
100.00 %
P0180 ... 199.99 %
2
0180.YY V/f character. Fmin
YY = The index which is displayed is determined by
the currently active setpoint memory.
0.00 %
0.00 % ... P0179
2
REFU internal 10036 Braking resistor
0 = REFU standard
1 = switched-out
2 = no protection
3 = can be externally programmed
0 ... 3
0623 Ext. BR: Resistance Supplementary parameters for brake resistor (P0036)
can be externally programmed
199.9 W
0.1 ... 199.9 W
2
0624 Ext. BR: Rated power Supplementary parameters for brake resistor (P0036)
can be externally programmed
1.0 kW
0.1 ... 199.9 kW
2
0625 Ext. BR: heatup time Supplementary parameters for brake resistor (P0036)
can be externally programmed
1.0 sec
1.0 ...655.4 sec
2