When using lime remover during cleaning, protective gloves and
goggles must be worn.
Chemical-resistant protective gloves
Chemical-resistant protective gloves are used to protect hands
from skin-irritating substances.
Protective goggles
Protective goggles are used to protect the eyes from splashes.
6.2 Cleaning schedule
The indicated time intervals apply for normal water
quality and normal dust occurrence in the air and
therefore may be longer or shorter.
Interval Maintenance work Personnel
Daily Check the water level. The device automatically switches off at a
residual water level of about 15 liters (4 gallons) (not applicable in
case of automatic water supply).
Operator
Check the humidity value using the control panel display. Operator
Monthly
Thoroughly clean the humidifier (
Ä
Chapter 6.3.1 “Monthly cleaning”
on page 40).
Operator
Every 3 to 4 months
Replace the evaporation filter (
Ä
Chapter 6.3.2 “Replacing the evap-
oration filter” on page 41).
Operator
Replace the activated charcoal cleaning filter (optional accessory)
(
Ä
Chapter 8.4.2 “Replacing the activated charcoal cleaning filter”
on page 64).
Operator
Clean the water tank (
Ä
Chapter 6.3.3 “Cleaning the water tank”
on page 44).
Operator
Annually Perform thorough cleaning of the device using lime remover
(
Ä
Chapter 6.3.4 “Decalcifying the device” on page 45).
Operator
Clean the UV degermination system and lime transforming cartridge
(optional accessory) (
Ä
Chapter 8.6.1 “Cleaning the UV degermina-
tion system and lime transforming cartridge” on page 67).
Operator
Protective gear
Cleaning and servicing the humidifier
Evaporation Humidifier B500 Professional 39