Entering system settings (Service menu – Settings)
6
RC35 programming unit - Technical specifications are subject to change without prior notice.
25
6.2 Boiler data
z Turn the rotary selector anti-clockwise until boiler data
is selected (marked with ).
z Press to select boiler data.
The menu SETTINGS \ BOILER is opened.
Menu item
Input range
Factory setting in bold
Other information
Boiler pump after-run
time after burner stops?
5min
Deactivated, 1 to 60 min
Setting only possible with boilers
with internal boiler pump.
1)
1) Not possible or not available with boilers with UBA1.x.
Which settings do you
wish to have for the mod-
ulating pump?
2
0 to 8
Characteristics of the boiler pump,
depending on KIM/BIM
0: if a hydraulic separator (low
loss header) has been installed.
1-8: see boiler documentation
1) 2)
2) System-dependent
Table 10 Navigator for Service menu SETTINGS \ BOILER
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1

Table of Contents

Other manuals for Buderus RC35

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus RC35 and is the answer not in the manual?

Buderus RC35 Specifications

General IconGeneral
DisplayLCD
Temperature ControlYes
Weather CompensationYes
CommunicationEMS Bus
MountingWall-mounted
Voltage24 V
Temperature range5°C to 30°C
Accuracy±0.5°C
Protection classIP20
Weight0.3 kg
Power consumption2 W
Switching currentNot applicable
Ambient temperature0°C to 45°C

Related product manuals