Entering system settings (Service menu – Settings)
6
RC35 programming unit - Technical specifications are subject to change without prior notice.
33
Shut-down mode: The boiler and the heating circuit pump are switched off, and frost
protection is activated. The heating circuit pump runs only for purposes of frost protec-
tion.
Not recommended if there is a risk that the building could cool down too much.
Room setback mode: If the room temperature falls below the set night temperature
(the target value), the heating system will operate in the same way as for reduced heat-
ing operation (as described under reduction mode "Reduced operation"). If the room
temperature exceeds the target night temperature by more than 1°K, the boiler and the
heating circuit pump are switched off (as described under reduction mode "Shut-down
mode").
This reduction mode is only possible if a programming unit / remote control unit has
been installed in a representative room (the reference room) or if the room temperature
is recorded using an external room sensor.
Outdoor setback mode: If the "delayed" response to outside temperature falls
below a user-defined outside temperature threshold, the heating system will operate in
the same way as for reduced heating operation (as described under "Reduced opera-
tion"). Above this threshold, the heating system will be switched off (as described
under reduction mode "Shut-down mode"). This reduction mode is suitable for heating
circuits which do not have their own programming unit / remote control unit. The oper-
ating mode protects the rooms from cooling down too much once a certain outside
temperature is reached.
6.3.5 Frost protection
The frost protection function comprises the following options:
No frost protection (frost protection is switched off)
Outside temperature (outside sensor required) If the outside temperature falls below
the threshold given by the set frost protection temperature, the heating circuit pump is
switched on automatically.
Room temperature
(room sensor in the RC35 / RC20) If the room temperature falls
below the fixed value of 5°C, the heating circuit pump is switched on automatically. If the
room temperature rises above 7°C, the heating circuit pump is switched off automatically.
Caution: System damage caused by freezing
The settings no frost protection and room temperature provide either no
frost protection or inadequate frost protection. When these settings are select-
ed, the display shows a message indicating the risk of freezing.
z For reliable frost protection, use the outside temperature setting.

Table of Contents

Other manuals for Buderus RC35

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Buderus RC35 and is the answer not in the manual?

Buderus RC35 Specifications

General IconGeneral
DisplayLCD
Temperature ControlYes
Weather CompensationYes
CommunicationEMS Bus
MountingWall-mounted
Voltage24 V
Temperature range5°C to 30°C
Accuracy±0.5°C
Protection classIP20
Weight0.3 kg
Power consumption2 W
Switching currentNot applicable
Ambient temperature0°C to 45°C