Monitor and control equipment
i-Vu CCN Pro 4.2 45
Setpoints
Programmed setpoints are set and changed by operators.
Effective setpoints reflect the impact of other system conditions on the programmed setpoints, such as
setpoint adjustments, and hysteresis. Effective setpoints control the equipment.
To change programmed setpoints:
1 Navigate to a setpoint control in one of the following places:
The Space Temperature Setpoints section of the Equipment tab of a Properties page
A Graphics page
2 On a programmed setpoint bar, click and drag the segment or the gap between segments you want to
change.
3 Type new values in the Heating and Cooling fields.
TIP You can click and drag a segment or a gap between segments to change setpoints.
4 Click OK.
To display or change driver or set driver properties
NOTE Only the Installer role has access to the following.