Synchronization Behavior of Analog Output
Module Configured as Floating Output
In order to regularly update the real actuator position with
the calculated position and thus ensure that the actuator
definitely reaches its end position, a synchronization pro-
cess is performed by the analog output module.
During the synchronization process, the analog output
module will continue running for the configured runtime
once it reaches the calculated end position.
This updating (synchronization) is performed:
If the calculated position of the actuator
< lower synchronization threshold (2 %)
= synchronization towards 0 %
If the calculated position of the actuator
> upper synchronization threshold (98 %)
= synchronization towards 100 %
Following any power-up or any reset