Chemtrol PC3000 - User Manual

Default Icon
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
MANUALPC-2012
i
© SBCS 2012
WARRANTY
This CHEMTROL® Controller S/N _________________ is warranted by SANTA BARBARA CONTROL SYSTEMS (SBCS) to be free
from defects in manufacturing and workmanship for a period of FIVE (5) YEARS from the date of purchase for the printed circuit boards
and ONE (1) YEAR for all other components. SBCS will repair or replace at its option any defective part during the warranty period.
Labor, shipping or incidental expenses are specifically excluded from this warranty. For warranty coverage, defective parts should be
returned immediately to your CHEMTROL® Dealer or to our factory postpaid with a copy of your purchase receipt and a description of
the malfunction.
800-621-2279
805-683-8833
TECHNICAL SUPPORT
US/CANADA
OTHER COUNTRIES
AUSTRALIA
EMAIL
1-300-585-820
support@chemtrol.com.au
INSTRUCTION MANUAL
CHEMTROL® PC PROGRAMMABLE
WATER TREATMENT CONTROLLERS

Table of Contents

Other manuals for Chemtrol PC3000

Questions and Answers

  • A
    Adrian McdanielAug 9, 2025
    Why can't I calibrate my Chemtrol PC3000 Controller?
    • D
      Derrick FitzgeraldAug 9, 2025
      If you are unable to calibrate your Chemtrol Controller, check the water balance and adjust if needed. Clean the sensor, and check the sensor connections. If problems persist, test the sensor and electronics using the PORTAPROBETM.
  • M
    msheaAug 14, 2025
    How to fix a Chemtrol Controller with no display?
    • J
      Jennifer AdamsAug 14, 2025
      If your Chemtrol Controller display is not showing anything, begin by checking the power supply to the system. Ensure that the On/Off Switch on the right side of the cabinet is in the correct position. Verify that the Voltage Selector Switch in the upper section of the Power Board is set to the proper input voltage (110V or 230V). Lastly, check Fuse F2 on the Power Board and replace it with an AGC1 fast blow fuse if it's blown.
  • B
    Barbara WheelerAug 18, 2025
    Why is my Chemtrol PC3000 causing chlorine or pH overfeed?
    • M
      Mark HallAug 18, 2025
      If you are experiencing chlorine or pH overfeed with your Chemtrol Controller, you should clean and test the sensor. Also, check and adjust the calibration and setpoint. Further, check the relay, the chemical feeder for leaks, and the Superchlorination Program. Finally, you may need to reduce the feed rate or dilute the solution.
  • M
    Michael DouglasAug 22, 2025
    How to adjust the contrast on a Chemtrol Controller display?
    • J
      Jonathan PearsonAug 22, 2025
      If the display on your Chemtrol Controller is faint or dark, adjust the contrast using the Display Potentiometer R39, which is located in the center of the Mother Board.
  • G
    Gerald RileyAug 26, 2025
    What to do if my Chemtrol Controller is showing improper readings?
    • J
      Julie MorganAug 27, 2025
      If your Chemtrol Controller is displaying improper readings, begin by cleaning the faulty sensor. If the issue persists, test the sensor and the electronics using the PORTAPROBETM.
  • L
    Lance MccannAug 31, 2025
    How to fix an erratic display on a Chemtrol PC3000 Controller?
    • C
      Christopher SmithAug 31, 2025
      If your Chemtrol Controller display is erratic, try turning the power switch off for 10 seconds and then back on. Also, check the power cable contacts and the power strip connecting the Mother Board and Power Board. Finally, press the program and memory chips on the Mother Board to ensure they have proper contact.
  • F
    fullerbenjaminNov 4, 2025
    What to do if Chemtrol Controller has no chemical feed, heater activation, or valve activation?
    • D
      Darryl HernandezNov 4, 2025
      If your Chemtrol Controller is not activating chemical feed, heater, or valves, first check the flashing line on the Main Display Screen. Use the UP or DOWN arrow to highlight it, then press the RIGHT arrow to enter the submenu and inspect the flashing line there. Possible causes include a LOW or HIGH ALARM flashing, in which case you should manually adjust the water chemistry or press the RIGHT arrow to change alarm limits, and consider setting Feed Lockout to Off. Alternatively, if the TIME LIMIT line is flashing, increase the chemical feeder rate, increase the Limit Timer setting, or reset the Time Limit with the AUTO setting. If the BYPASS LINE is flashing on the Main Display, check water flow and the Safety Flow Switch in the bypass line, or set Bypass Line to Off in the Operations Su...

Summary

Important Safety Instructions

Chapter II - Installation

Chapter III - Startup

Controller Initial Setup and Configuration

Steps for initial controller startup, configuration, and sensor activation procedures.

Chemical Control Adjustments and Calibration

Procedures for adjusting water chemistry, calibrating sensors, and setting chemical control parameters.

Chapter IV - Operation

Chapter V - Communications

Chapter VI - Maintenance

Controller and Sensor Maintenance

Routine maintenance for the controller, sensors, battery, and software upgrades.

Chemical Maintenance and Testing

Guidelines for maintaining water chemistry and performing periodic water testing and shock treatments.

Troubleshooting Guide

Display and Feed Issues

Diagnosing and resolving common problems with the display, chemical feed, and heater activation.

Chemtrol PC3000 Specifications

General IconGeneral
TypeController
pH ControlYes
ORP ControlYes
Temperature ControlYes
Langelier Saturation Index (LSI) CalculationYes
Heater ControlYes
AlarmsYes
Data LoggingYes
Remote MonitoringYes
Enclosure RatingNEMA 4X
DisplayLCD
Input Voltage120-240V AC
Communication ProtocolModbus
Operating Temperature0-50°C