Loading...
function
code
name
Attributes
Detailed description of parameters
default
value
F0.20
parameter
initialization
0: invalid operation
1: Clear fault record information
2: Restore factory parameters ( except motor parameters )
3 : Restore factory defaults for custom parameters ( except
motor parameters )
4: All parameters restore factory defaults
5: Backup parameters
6 : Use backup parameters
7 : Save backup parameters
Note: Only when the backup parameters are used, the
backup parameters can be saved; otherwise, after power
-off and power-on, except for the modified parameters,
other parameters will still be the original parameter values.
0
F2.00
Motor Type Selection 0: Ordinary asynchronous motor
0
F2.01
Motor rated power
(0.1 ~ 1000.0) kW
Model
confirmed
F2.02
Motor rated voltage 1 V ~ inverter rated voltage
Model
confirmed
F2.03
Motor rated current
(0.01600.00)A (inverter power<=55kW)
(0.16000.0)A (inverter power>55kW)
Model
confirmed
F2.04
Motor
rated frequency
0.01Hz ~ F0.07
Model
confirmed
F2.05
Number of
motor poles
2 to 24 4
F2.06
Motor rated speed
(065535)rpm
1430rpm
F2.22
Motor parameter
self-learning
0: no operation;
1: Motor static self-learning;
2: Motor dynamic self-learning
0
7.3.2 Basic debugging process
   The basic debugging process is shown in Figure 7-10