Figure C: Recommended placement – Standard configuration 14-18kVA (overhead view)
UPS
CABLE ENTRY (BOTTOM)
FRONT
BATTERY
CAB
1.5.1 SPECIFICATIONS FOR HANDLING EQUIPMENT
The Electronics Module can be moved into place by one or two persons. See Table
A
for
unit weights.
1.5.2 SPECIFICATIONS FOR UTILITY INPUT LINE AND RATINGS
This system must be connected to a properly rated 60Hz +/- 5% line. Voltage tolerance
must be +/- 10% of nominal. Refer to Table
B
for the proper input current rating.
1.5.3 INSTALLATION DATA
- Ambient temperature 0 °C to +40 °C (32 °F to 104 °F)
- Relative humidity (w/o condensing at 20°C) 90%
- Maximum altitude without derating 1000 m (3300 ft)
- Cable entrance bottom at rear
- Air inlet bottom
- Air outlet rear