5.0 Specifications
5.1 ELECTRICAL
5.1.1 SYNTHESIS 4-12kVA
(At 25 °C, Nominal Line Voltage unless otherwise specified)
Output Power (kVA/kW): 4/2.8, 5/3.5, 6/4.2, 8/5.6, 10/7, 12/8.4
Input Voltage: 208* or 240 VAC, 60 Hz, Single Phase Factory Wired
*NOT AVAILABLE ON 6kVA or 12kVA SYSTEMS
Output Voltage: 120/208/240V Single Phase Factory Wired
Output Frequency: 60 Hz ± 0.05%
Output Voltage Regulation: ± 6%
(Static)
Dynamic Output Voltage 5% (0-100% AND 100%-0 Load
Regulation: Variation)
(Over Static Regulation)
Charging Current: 1A (4-6kVA)
2A (8-12kVA)
Efficiency:
Measured at Rated Load, 0.7 pf
Line Interactive Mode: 93%
Double Conversion Mode: 87% (4-6kVA)
88% (8-12kVA)