Table A: UPS Installation with standard battery
DESCRIPTION Unit of
Measure
UPS Size
(kVA)
UPS Rating kVA 4-6 8-12 14-18
Cabinet
UPS Output UPS Output UPS
Length in 19.5 19.5 24.6 24.6 23.6
Width* in 14.2 10 17.7 12 33.0
Height in 30.3 30.3 38.2 38.2 43.5
Weight
lb. 200 135 477 152 340 425
Total weight lb. 335 632 340 425
Floor loading lb/ft
2
102 124
Extracted volume of air Ft
3
/min 97 119 255
Max. noise level (@ 1m) dBA 48 50 52
Terminal Torque:
Line and neutral
Ground
Pound-
inches
13
13
20
13
39
13
Unit size 4 5 6 8 10 12 14 16 18
Maximum dissipation
(@ normal load and battery
in recharge )
W 260 330 400 490 610 730 2150 2458 2766
1.5.4 STORAGE DATA
Temperature limits - batteries 0°C to +35°C (32°F to 88°F)
Temperature limits - electronics -20°C to +70°C (0°F to 144°F)
Relative humidity from 0% to 90%
1.5.5 EXTERNAL PROTECTION DEVICES AND WIRE SIZES
The Synthesis™ UPS does not contain branch overcurrent protection devices on either its
input or output. It is the responsibility of the installer to provide this protection. Read the
following sections carefully, following NEC and local codes in all cases if there is a conflict
with this document.
External devices for the protection of cables external to the UPS shall be installed
upstream of the equipment.
CAUTION
To reduce the risk of fire, only connect this UPS to a circuit provided with maximum
branch circuit overcurrent protection as specified in Table B below and in accordance
with the National Electrical Code, ANSI/NFPA 70.