Figure 60: Attaching the Left Door Stopper
Screw holes on the cable management
frame.
3Left door stopper identified with an L on the bottom of the base.1
Two M3x10 screws that fasten the stopper to the cable management
frame.
2
Step 2 Position the right door stopper (700-27592-01) on the middle of the right side of the cable management frame and
fasten it with two M3x10 pan-head screws as shown in Figure 61: Attaching the Right Door Stopper, on page 117.
Tighten these two screws to 5 to 7 in-lb (0.6 to 0.8 N·m).
Cisco Nexus 7000 Series Hardware Installation and Reference Guide
116
Installing a Cisco Nexus 7018 Chassis
Installing the Front Door and Air Intake Frame