This setpoint is used to adjust the nominal busR voltage (phase to neutral). If 
you do not know the phase-neutral nominal voltage, you can adjust the 
phase-phase nominal voltage busRNomVph-ph. The controller will then 
recalculate the phase-neutral nominal voltage automatically. 
NOTE:  
The actual setpoint units and range depend on setting of the Power format in 
GenConfig. 
 
NOTE:  
If different voltage on BusL and on BusR is required the following procedure 
is required:  
Both setpoints (BusRNomV and BusLNomV) must be adjusted to the same 
values according to the value of actual BusL or BusR nominal voltage. E.g. 
BusR nominal is 231 V but BusL nominal is 240 V.  
In this case both setpoints need to be adjusted to 231 V and setpoints of 
corresponding protections for BusL need to be set assymetrically.  
For 240 V on BusL it is typical to open BTB when voltage reaches 254 V or 
225 V. Since the setpoint is adjusted to 231 V corresponding protection 
setpoints need to be adjusted to BusRight >V = 106% and BusRight <V = 97 
% (hence the desired values are reached).  
 
This setpoint is used to adjust the nominal busR voltage (phase to phase). 
This setpoint is also recalculated automatically when the phase-neutral 
nominal voltage busRNomV is changed. 
This setpoint can be used if you know the phase-phase nominal voltage only. 
The controller will recalculate the phase-neutral nominal voltage