The setpoint adjusts nominal system frequency (choose 50 Hz or 60 Hz).  
Setpoint Nom frq offset is used for setting offset to the chosen nominal 
frequency (-2 to +2 Hz with step 0.01 Hz). Controller regulates to the Nominal 
Freq + Nom frq offset frequency.  
The value Nominal Freq + Nom frq offset is used as 100% for frequency 
protections.  
 
12.2.2.17  Setpoint: ControllerMode 
This setpoint can be used to select the controller mode. It is equivalent to 
selecting the mode by the buttons on the front panel or IntelliVision. Currently 
active mode is displayed on the controller main screen. 
NOTE:  
If any of the mode forcing inputs Remote OFF, Remote MAN or Remote AUT 
is active, then the currenly active mode can be different than the mode 
selected by the setpoint (resp. panel buttons).  
 
 
All regulations are switched off.  
Switching to OFF mode causes opening of BTB regardless of 
the settings.  
It is possible to close/open BTB manually under supervision of 
IM-NT controller which doesn’t allow to close the breaker if the 
bus voltages are not in phase (synchronization starts upon 
pushing BTB close/open button).  
Pressing BTB ON/OFF button closes/opens BTB if it is 
allowed by  
  setpoints Synchro enable, Mains coupling, 
DeadBusClosing 
  binary input BTB disable 
Controller closes automatically BTB if  
  bus voltages are within the limits (Phase window, 
Voltage window)  
  there is voltage on one of the buses and closing to dead