12.2.3.3  Setpoint: Contr. address 
This setpoint adjusts the address of the particular controller at the CAN2 
and/or RS485 bus. Each gen-set connected to the same bus must have 
unique address. 
If the setpoint CANnegotiation is in AUT position, the address is assigned 
automatically. The setpoint Contr. address is preffered then, however if it is in 
conflict with other controller present on the CAN2 bus other address will be 
assigned to aviod address collision. 
NOTE:  
Address 1 is reccommended for standalone gen-sets. 
 
NOTE:  
If you are connecting to the controller remotely you have to adjust the proper 
controller address in connection settings of the remote client (InteliMonitor, 
GenConfig, Modbus client etc.)  
 
NOTE:  
Address of the controller is also used for Modbus communication via RS485 
etc. Address adjusted by this setpoint is therefore universal address of the 
controller.  
 
 
12.2.3.4  Setpoint: RS232(1) mode 
DIRECT, MODEM (HW), MODEM (SW), MODBUS-DIRECT, MODBUS-
MDM(HW), ECU LINK [-]  
This setpoint selects the connection type for the serial port COM1.  
  Available as RS232 in all controller types. 
  Available also as RS485 in the IG-NT if the external display bus is 
not used. Selectable by the setpoint RS485(1) conv. (not available in 
IG-NT-BB, IG-NTC-BB, IS-NTC-BB and IS-NT - see RS485(1) 
conv.).  
See the diagram of all related terminals in the chapter Communication.