14.2.1.50  Binary input: ExtValue2 down 
While this input is active the value of ExtValue 2 is contiously beeing 
decreased at the rate of ExtValue2 rate until it reaches ExtValue2LoLim. 
NOTE:  
If this input is used (configured), the ExtValue 2 can't be written remotely 
from a remote terminal using the command ExtValue 2.  
 
 
14.2.1.51  Binary input: ExtValue3 up 
While this input is active the value of ExtValue 3 is contiously beeing 
increased at the rate of ExtValue3 rate until it reaches ExtValue3HiLim. 
NOTE:  
If this input is used (configured), the ExtValue 3 can't be written remotely 
from a remote terminal using the command ExtValue 3.  
 
 
14.2.1.52  Binary input: ExtValue3 down 
While this input is active the value of ExtValue 3 is contiously beeing 
decreased at the rate of ExtValue3 rate until it reaches ExtValue3LoLim. 
NOTE:  
If this input is used (configured), the ExtValue 3 can't be written remotely 
from a remote terminal using the command ExtValue 3.  
 
 
14.2.1.53  Binary input: ExtValue4 up 
While this input is active the value of ExtValue 4 is contiously beeing 
increased at the rate of ExtValue4 rate until it reaches ExtValue4HiLim. 
NOTE:  
If this input is used (configured), the ExtValue 4 can't be written remotely 
from a remote terminal using the command ExtValue 4.