Description
This is the flashing alternative of the output Alarm, i.e. the output flashes with
period 1s/1s while the output Alarm is closed.
15.2.1.32 Binary output: Horn flashing
Related FW
3.0
Description
This is the flashing alternative of the output Horn, i.e. the output flashes with
period 1s/1s while the output Horn is closed.
15.2.1.33 Binary output: FltResButnEcho
Related FW
3.0
Description
This output provides 1s pulse when:
Fault reset button is pressed on the controller front panel or
Fault reset button is pressed on any of external local/remote
terminals or
fault reset command is received via communication line or
the input FaultResButton is activated.
15.2.1.34 Binary output: HrnResButnEcho
Related FW
3.0
Description
This output provides 1s pulse when:
Horn reset button is pressed on the controller front panel or
Horn reset button is pressed on any of external local/remote
terminals or
horn reset command is received via communication line or
the input HornResButton is activated.
15.2.1.35 Binary output: BTBButnEcho
Related FW
3.0
Description
This output provides 1s pulse when:
BTB button is pressed on the controller front panel or
BTB button is pressed on any of external local/remote terminals or