Setpoint group Engine protection Related FW 2.5.0
Range [units] NORMAL, CLASS C [-]
Default value NORMAL -
Step -
Comm object 13076 Related applications
Description
NORMAL
Protection behaves according to the standard configuration of Wrn/Sd alarm in
LiteEdit AINx configuration screen. Default state.
CLASSC
The protection is type Running only” and does not depend on Running only tick in
LiteEdit AINx Alarm properties configuration window. Protection (Class C) is
working after AINx Del or sooner when appropriate value increases over AINx Wrn
limit +3 seconds - after engine start. Warning/ShutdDown protection is activated
with fix delay 0.5s.
Note: Class C protection is working and corresponding setpoints are visible only when corresponding
AIN is configured in Modify->Alarm properties-> Direction-> Window prot.
AIN6 Eval
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 10000 [U12]
Default value 20 -
Step 1
Comm object 13359 Related applications
Description
Low Warning limit level for AIN6.
AIN6 LowWrn
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 ... 10000 [U12]
Default value 10 -
Step 1
Comm object 13360 Related applications
Description
Low ShutDown limit level for AIN6.
AIN6 LowSd
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals