ID-FLX Lite & Telecom Global Guide
154
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 3600 [s]
Default value 10 -
Step 1
Comm object 13349 Related applications
Description
High level protection delay for Wrn and Sd of AIN7.
Note: In the alarm list is only displayed Wrn/Sd alarm on the appropriate analog input. There is not
resolution Low/High alarm.
Note: Analog input 7 is fully configurable and it is voltage type of input with range 0-10V.
AIN7 HighDel
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 10000 [U14]
Default value 20 -
Step 1
Comm object 9265 Related applications
Description
Warning limit level for AIN8.
AIN8 Level 1
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 10000 [U14]
Default value 20 -
Step 1
Comm object 9266 Related applications
Description
Shutdown limit level for AIN8.
AIN8 Level 2
6 back to List of setpoints