174
Setpoint group Sensors Spec Related FW 2.5.0
Range [units] [Always /Running /OFF]
Default value OFF -
Step -
Comm object 14283 Related applications
Description
Setting of Counter 1 and Counter 2 mode:
Always Corresponding counter counts pulses all time.
Running Corresponding counter counts pulses only when engine is running.
OFF Corresponding counter does not count pulses. Default settings.
Note: The Total 1 and Total 2 values are visible in LiteEdit Values Statistics.
The Total 1 and Total 2 values disappear from controller screen when both Counter modes 1 and 2 are
switched OFF otherwise there is new screen between existing Statistics and Alarm list.
Counter mode 1, Counter mode 2
6 back to List of setpoints
Group: AIO module
Setpoint group AIO module Related FW 2.5.0
Range [units] -100 .. 10000 [-]
Default value 0 -
Step 1
Comm object 13650 Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO1 lev1
6 back to List of setpoints
Setpoint group AIO module Related FW 2.5.0
Range [units] -100 .. 10000 [-]
Default value 0 -
Step 1
Comm object 13651 Related applications
Description
The level for il-nt plug-in card Analog input 1, 2, 3, 4 alarm detection.
AnlInAIO2 lev1
6 back to List of setpoints