State Condition of the transition Action Next state
Not Ready
RPM < 2, Oil pressure not detected, D+ not
Active, no shutdown alarm active, other than OFF
mode selected
Ready
Prestart
1
Prestart time elapsed
STARTER on
FUEL SOLENOID on
2
MaxCrank time
counter started
Cranking
Cranking
1
RPM >Start RPM AND BI: Nominal/Idle is active
STARTER off
PRESTART off
Starting
RPM >Start RPM AND BI: Nominal/Idle is not
active
STARTER off
PRESTART off
READY TO LOAD on
Running
D+ input activated for 1s or oil pressure detected
STARTER off
PRESTART off
Cranking
MaxCrank time elapsed, 1st attempt
STARTER off
FUEL SOLENOID off
STOP SOLENOID on
CrankFail pause timer
started
Crank pause
MaxCrank time elapsed, last attempt
STARTER off
PRESTART off
Shutdown (Start
fail)
Crank
pause
1
CrankFail pause elapsed
STARTER on
FUEL SOLENOID on
2
STOP SOLENOID off
MaxCrank time
counter started
Cranking
Starting
1
NOMINAL/IDLE (PAGE 189) is active
FUEL SOLENOID on
2
STOP SOLENOID off
READY TO LOAD off
Starting
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
Shutdown
Stop time elapsed or Engine stopped + 10s
elapsed
FUEL SOLENOID off
STOP SOLENOID on
Shutdown (Start
fail)
Running
Stop request
READY TO LOAD off
Cooling time timer
started
Cooling
NOMINAL/IDLE (PAGE 189) is active
FUEL SOLENOID on
STOP SOLENOID off
READY TO LOAD off
Running