InteliMains 210 Global Guide
139
Alarm Email
The InteliMains 210 controller equipped with the CM-Ethernet communication module is able to send Alarm
Emails according to the setting of setpoints:
Wrn Message (page 287)
Sd Messages (page 287)
BOC Message (page 287)
Note: Firstly setpoints Email Address 1 (page 284) and SMTP Sender Address (page 279) (for CM-GPRS) or
SMTP Sender Address (page 289) (for CM-Ethernet) have to be adjusted.
Note: #Summer Time Mode (page 248) and Time Zone (page 286) have to be adjusted for correct time in emails.
Message structure:
Controller
-----------------------------------------------
Name: XXX
Serial number: XXX
SW branch: XXX
SW version: XXX
Application: XXX
Appl. version: XXX
Date: dd/mm/yyyy
Time: hh:mm:ss
Alarm list
-----------------------------------------------
Alarm 1
Alarm 2
Alarm 3
History events
-----------------------------------------------
0 dd/mm/yyyy hh:mm:ss.0 Event 1
-1 dd/mm/yyyy hh:mm:ss.0 Event 2
-2 dd/mm/yyyy hh:mm:ss.0 Event 3
Note: Asterisk means that alarm is unconfirmed and exclamation mark means that alarm is active.